Firmware Update
Contact Racktivity Support
To obtain the necessary software to update your device firmware,
please contact Racktivity Support:
US: us_support@racktivity.com
Europe: eu_support@racktivity.com
- Make sure that your computer and the device are on the same network and fully functional.
- Unpack the update package.
- Open the software tool "Racktivity Ethernet Bootloader.exe"
- Use the "File" button to select the .cry file that came with the update package.
- Fill in the appropriate IP address and login credentials of the designated EnergySwitch.
- Press "Update firmware" to start the update.
- The update has successfully completed when "Programming completed / Exit bootloader" is shown (the update takes a few minutes).
Troubleshooting
IF:
After starting the update "FAILED (check Settings)" is shown
Please make sure that:
- The device is powered on and connected to LAN with a correct IP address.
- You entered the correct login credentials under "Settings" in the software tool.
- You are on the same LAN as the EnergySwitch.
To verify the above settings are correct, go to the Web Portal and log in.
IF:
The Status window continuously shows output similar to "**ERROR Out of Sequence PDU Seq: 5294 5299"
- This is a mere warning and does not compromise the update.
IF:
The update fails and the device becomes unresponsive.
- If needed: restore power and/or ethernet to the device.
- Repeat the steps above to start the update again.
- In case you need to know the IP address, and it can not be retrieved using the regular methods, (Determine IP Address), then:
- Connect a console cable between the device and your pc.
- Use the following settings to read the output: Baudrate 38400, 8 databits, no parity, 1 stopbit.
- Reboot the device, the currently used IP address is shown in the console output.
- Repeat the steps above to start the update again.